VG 95218/PART 60 (MGSGO)

PENDANT CABLES
May 15, 2020
VG 95218/PART 61 (LMGSGO)
May 18, 2020

VG 95218/PART 60 (MGSGO)

Fixed installation cable for power, control and lighting.

Download Pdf
CONDUCTOR : Electrolytic, stranded, tinned copper wire IEC 60228 Class 2 (Class 5 on request).
INSULATION : Halogen free EPR or Halogen free HEPR
BEDDING : Halogen free compound.
SCREEN : Electrolytic, tinned copper braided screen ( 90% coverage ).
OUTER SHEATH : Halogen free, cross-linked polyolefin compound. Mud resistant on request.
CONSTRUCTION : VG 95218 TEIL 60
TESTS AND MATERIAL : IEC 60092 /350-351-359, VG 95214, VG 95218/60
FLAME RETARDATION : IEC 60332 /1, IEC 60332 / 3 Cat A
HALOGEN CONTENT : IEC 60754 / 1 – 2
SMOKE DENSITY : IEC 61034 / 1-2 ( DIN EN 50268/1-2)
WORKING TEMPERATURE : -40°C / + 90°C
MIN. BENDING RADIUS (FIXED) :x 8 x(overall diameter)
RATED VOLTAGE : 1,2 kV
TEST VOLTAGE : 3,5 kV
CROSS SECTION (mm2) OVERALL DIAMETER (mm) APPX. WEIGHT (kg / km) COPPER WEIGHT (kg / km)
1X1611.6310209
1X12513.3430310
1X1614.3540416
1X5016.2705580
1X7017.9925787
1X9520.11.211042
1X12022.21.51302
1X15024.21.821600
1X18526.22.21956
1X24029.62.862504
2X1.513.2300109
2X2.514335138
2X415.2410172
2X616.4490226
2X1018.2630312
2X1620.8850448
2X2524.41.2640
3X1.513.8320129
3X2.514.6380167
3X415.9460216
3X617.2560283
3X1019.3750418
3X1621.91.02611
3X25261.47898
3X3528.51.841203
3X5032.52.451670
3X7036.93.282276
3X9542.44.433136
3X12045.85.353896
3X15049.36.34810
4X1.514.8380153
4X2.515.7440201
4X417.4560264
4X618.6680356
4X1021920529
4X1624.11.275780
4X2528.61.851158
4X3531.22.31559
4X5036.83.22265
4X7041.34.243078
4X95475.64093
 
Seabright SA